Which Buildings
Regulation 10 of the Fire Safety (England) Regulations 2022 has applied since 23 January 2023. Its information duties cover every building with two or more sets of domestic premises and common parts that residents would use to escape. Its routine checks apply only where the building also has a top storey more than 11 metres above ground level, which government guidance describes as typically more than four storeys.
Communal Fire Doors: Every Three Months
The responsible person must check the fire doors in the communal areas at least every three months, including checking that their self-closing devices work.
Flat Entrance Doors: Best Endeavours, Every 12 Months
For the entrance door of each flat, the duty is to use best endeavours to check it at least every 12 months, again including the self-closing device. Getting to the door depends on the resident letting you in, which is why the duty is framed as best endeavours rather than an absolute requirement.
When You Cannot Get In
Government guidance leaves the approach to the responsible person, for example by agreeing a date with the resident. Where access cannot be achieved, it expects evidence of the steps taken. The Regulations require a record of the steps taken to check flat entrance doors in each 12-month period, including the steps taken where a resident did not give access.
In practice that record is a dated log of each letter, email and visit, and of the resident’s response. It is the evidence that the duty was attempted where the check itself could not be made.
What a Check Is, and What It Is Not
These are simple visual checks. Government guidance says they do not need a detailed technical examination or a specialist: with simple instruction, the responsible person or their staff should be able to carry them out. Whether a door gives the fire resistance it should is a matter for the fire risk assessment.
Where a check finds a fault, the repair or replacement should be carried out by a competent contractor as soon as reasonably practicable. The guidance is also clear that a fire door does not have to be replaced simply because it does not meet the current standard under building regulations, if it remains in full working order from a fire safety point of view.
Information for Residents
In any building with two or more flats and shared escape routes, residents must be told that fire doors should be kept shut when not in use, that they should not tamper with self-closing devices, and that faults should be reported immediately. New residents must be told as soon as reasonably practicable after they move in, and all residents within each 12-month period.
LEGAL BASIS
Fire Safety (England) Regulations 2022
Regulation 10 requires responsible persons for multi-occupied residential buildings above 11 metres to undertake quarterly checks of fire doors in common parts and to make best endeavours to check flat entrance doors annually. In all other buildings the duty flows from the fire risk assessment under the Fire Safety Order.
Where Haven Fits
The routine checks can be done in-house. Haven’s fire door inspection is a separate, more detailed survey for blocks, HMOs and commercial buildings, recording gaps, seals, hardware and closers door by door. It can sit alongside the routine checks, but it does not replace your own record of them.